Inspection, Maintenance & Servicing

Service Scheduling 

BRUSH Service is fully equipped to provide all existing operators with a comprehensive, standard or bespoke support package, that may be adapted to suit each and every individual operator’s need, wherever the installation be situated.

 

Regular Maintenance

The notion that "prevention is better than cure" lies at the heart of any maintenance programme. Regular maintenance may be categorised into the following terms:

  • Preventative maintenance utilising regular inspection packages bespoke to the customer's planned outage periods and the holding of strategic stock of parts.
  • Predictive maintenance utilising specific maintenance based on regular inspections and assessments of equipment condition and replacement material requirements.
  • Life-cycle maintenance utilising maintained stock of parts and exchange of strategic parts.

 

Service Interval

Detail

Minor Inspections

8,000 hrs or 1 year *

Typically includes basic checking of protection and monitoring devices.

25,000 hrs or 3 years *

Typically includes additional checking of exciter, rectifier and cooling systems.

50,000 hrs or 6 years *

Also completed with the rotor in-situ, this typically includes the minor inspections and additional checks of the bearing and stator end winding.

75,000 hrs or 9 years *

Similar to 25,000 hours inspection.

Major Inspections

100,000 hrs or 12 years *

Similar to 25,000 hours inspection this is the most comprehensive generator inspection and includes the removal and inspection of the rotor.

Rotor endcaps (endrings) may be removed and we may complete a boroscope inspection, depending on your equipment. With the rotor removed, a thorough stator core inspection can be completed to check stator coil, wedge and insulation condition.

* Frequency of inspection may be adjusted to suit the customer’s maintenance schedule and the number of starts.

     

    Interested in more information? Please get in touch.

    Contact UsContact